KromschroderBurner Controls
Kromschroder Gas Filter Gfk
27 sizes & variants — select below · Connection: 5 options
Kromschroder Gas Filter GFK 65R40/6
EXW Singapore
Collect or forward from our office
Lembar Data Atas Permintaan
Spesifikasi teknis
Penawaran 1 Hari
Balasan dalam 24 jam
Local availability & support — Indonesia
- Phone
- +65 8878 8355
From the manufacturer's datasheet
KromschroderMax. inlet pressure pe
1 bar (GFK up to DN 250), 4 bar (GFK up to DN 150), 6 bar (GFK up to DN 100)
Operating temperature
-15 °C to +80 °C
Filter pad material
Polypropylene fleece, 50 µm standard
Housing material
AlSi (DN 15 to DN 100), welded sheet steel (DN 125 to DN 250)
Connections
Threaded Rp to ISO 7-1 (DN 15-65), Flanged to ISO 7005, PN 16 (DN 40-250)
Pressure test points
Inlet Rp 1/8, outlet plugged or un-drilled, test point on cover
Weight range
0.4 kg (DN 15) to 130.0 kg (DN 250)
Filter dimensions
Various, e.g., 127 x 56 mm (DN 15) to 908 x 417 mm (DN 250)
Features
- High purification efficiency
- Very high throughput
- Long service life
- Filter pad easily cleaned
- Suitable for horizontal and vertical pipe installation
Typical applications
Filtration of fuel gas and combustion air for gas appliancesProtection of downstream devices against blockage
Continuous operation at high temperatures accelerates the ageing of elastomer materials.
Select a size
Showing 27 / 27 variants — scroll the table for more
| Part No (MPN)15R106 | 3G SKU3G-CBM-04439 | ConnectionRp ½ | |
| Part No (MPN)20R106 | 3G SKU3G-CBM-04440 | ConnectionRp ¾ | |
| Part No (MPN)25R106 | 3G SKU3G-CBM-04441 | ConnectionRp 1 | |
| Part No (MPN)40R106 | 3G SKU3G-CBM-04443 | ConnectionRp 1 | |
| Part No (MPN)50R106 | 3G SKU3G-CBM-04444 | ConnectionRp 1 | |
| Part No (MPN)65R106 | 3G SKU3G-CBM-04445 | Connection— | |
| Part No (MPN)40F106 | 3G SKU3G-CBM-04446 | Connection— | |
| Part No (MPN)50F106 | 3G SKU3G-CBM-04447 | Connection— | |
| Part No (MPN)65F106 | 3G SKU3G-CBM-04448 | ConnectionRp 1 | |
| Part No (MPN)80F106 | 3G SKU3G-CBM-04449 | ConnectionRp 1/2 | |
| Part No (MPN)100F106 | 3G SKU3G-CBM-04450 | Connection— | |
| Part No (MPN)125F103 | 3G SKU3G-CBM-04451 | Connection— | |
| Part No (MPN)150F103 | 3G SKU3G-CBM-04452 | Connection— | |
| Part No (MPN)200F103 | 3G SKU3G-CBM-04453 | Connection— | |
| Part No (MPN)250F103 | 3G SKU3G-CBM-04454 | Connection— | |
| Part No (MPN)15R406 | 3G SKU3G-CBM-04455 | ConnectionRp 1/2 | |
| Part No (MPN)20R406 | 3G SKU3G-CBM-04456 | ConnectionRp ¾ | |
| Part No (MPN)25R406 | 3G SKU3G-CBM-04457 | ConnectionRp 1 | |
| Part No (MPN)32R406 | 3G SKU3G-CBM-04458 | ConnectionRp 1¼ | |
| Part No (MPN)40R406 | 3G SKU3G-CBM-04459 | ConnectionRp 1/2 | |
| Part No (MPN)50R406 | 3G SKU3G-CBM-04460 | ConnectionRp 1/2 | |
| Part No (MPN)65R406 | 3G SKU3G-CBM-04461 | Connection— | |
| Part No (MPN)40F606 | 3G SKU3G-CBM-04462 | ConnectionRp 1 | |
| Part No (MPN)50F606 | 3G SKU3G-CBM-04463 | ConnectionRp 1 | |
| Part No (MPN)65F606 | 3G SKU3G-CBM-04464 | ConnectionRp 1 | |
| Part No (MPN)80F606 | 3G SKU3G-CBM-04465 | ConnectionRp 1 | |
| Part No (MPN)100F606 | 3G SKU3G-CBM-04466 | ConnectionRp 1¼ |
Tidak yakin ini adalah suku cadang yang tepat? Minta rekomendasi.
Ask a question
Minta PenawaranAjukan pertanyaan
Pertanyaan yang Sering Diajukan
What types of gas can the GFK filter handle?
Natural gas, town gas, LPG (gaseous), biologically produced methane, and air.
What is the standard filter pad rating?
The standard filter pad is 50 µm, EC type-tested and certified.
What are the maximum inlet pressures for different sizes?
1 bar for GFK up to DN 250, 4 bar for GFK up to DN 150, and 6 bar for GFK up to DN 100.