Konten Lembar Data
GAS BURNERS LOW NOX (CLASS 4) TWO STAGES PROGRESSIVE SK073074_A_en
OR MODULATING WITH ELECTRONIC CONTROL BOX mod: GAS P130/MCE LX4 EL EVO
GAS P160/MCE LX4 EL
GAS P130/MCE LX4 EL EVO - GAS P160/MCE LX4 EL
Gas burners with electronic control box. Two stages progressive or modulating operation (if equipped with addition
of optional modulation kit PID and probe; to guarantee an ideal proportionality of the power supplied to the
thermal load).
Composed by: die-cast aluminum body ,high pressurisation air blower and combustion head at high efficiency and
high flame stability. Compact overall dimensions and disposition rationalized of the components with accessibility
facilitated for easy setting and maintenance.
Available in the versions METHANE (natural gas) or L.P.G. (to specify at the order).
Gas train completely assembled and tested; composed by working valve with flow adjustment, safety valve,
minimum gas pressure switch, valve proving system and gas filter + gas pressure stabiliser.
Complete of flange and gasket for installation on generator.
The servomotors are indipendent and managed directly from the electronic control box of the burner: one servomotor
for the gas modulator and one servomotor for the air shutter.
The burners are equipped with a display that allows to:
- adjust the operating parameters of the burner
- visualize the flame intensity
- adjust the operating curve of the burner (air / gas ratio)
With the addition of optional accessories (probes) thanks to the most advanced systems for automatic modulation in
mechanical or electronic version, the burner constantly ensures the proper gas / air ratio.
The maximum efficiency of the returns in each combustion point derived from the punctual adaptation of the thermal
load to the heat requirements of the burner at any instant of operation.
In the version with the electronic cam the fuel / combustion air curve, more extended, is fully exploited, guaranteeing
excellent performance in terms of accuracy and speed, even during the calibration phase.
A microprocessor monitors the different stages of the process and allows the correct repetition of the sequences of
operation.
Optional accessories: PID power modulator kit, probe, PC interface, VSD, O2 control, O2 + CO control, field bus
(profibus, modbus, profinet).
Fig. GAS P130/MCE LX4 EL EVO
GAS P130/MCE LX4 EL EVO - GAS P160/MCE LX4 EL
GAS BURNERS LOW NOX (CLASS 4) TWO STAGES PROGRESSIVE SK073074_A_en
OR MODULATING WITH ELECTRONIC CONTROL BOX mod: GAS P130/MCE LX4 EL EVO
GAS P160/MCE LX4 EL
CONTROL BOX LAMTEC BT3
Fig. Control box Lamtec BT3
GAS P130/MCE LX4 EL EVO - GAS P160/MCE LX4 EL
GAS BURNERS LOW NOX (CLASS 4) TWO STAGES PROGRESSIVE SK073074_A_en
OR MODULATING WITH ELECTRONIC CONTROL BOX mod: GAS P130/MCE LX4 EL EVO
GAS P160/MCE LX4 EL
TECHNICAL DATA GAS P130/MCE LX4 EL EVO - NATURAL GAS -
MODEL GAS P130/MCE LX4 EL EVO
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 241/612-1247
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 280/712-1450
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 28.2/71.5-146
Fuel: NATURAL GAS (second family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
Intermitted working operation (min. 1 stop every 24 hours) modulating
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Min. pressure gas train D2"-S NATURAL GAS ** [mbar] 52.8
Min. pressure gas train D2"-S MBE NATURAL GAS ** [mbar] --
Min. pressure gas train DN65-FS65 NATURAL GAS ** [mbar] 35.5
Min. pressure gas train DN80-FS80 NATURAL GAS ** [mbar] 29.8
Maximum pressure at the entry of valves (D2") [mbar] 360
Maximum pressure at the entry of valves (D2" MBE - DN65 - DN80) [mbar] 500
Nominal electric power [kW] 2.4
Fan motor [kW] 2.2
Nominal motor current absorption [A] 4.35
Nominal auxiliary absorption [A] 0.7
Power supply: 3~400V, 1/N~230V-50Hz
Electric protection degree: IP 54
NOx Class, NATURAL GAS (second family) 4
Noisiness *** min. - max. [dB(A)] 81-82
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law -
Control method class 3 - The measured sound pressure tolerance can be assumed to be ± 1 [dB (A)]).
GAS P130/MCE LX4 EL EVO - GAS P160/MCE LX4 EL
GAS BURNERS LOW NOX (CLASS 4) TWO STAGES PROGRESSIVE SK073074_A_en
OR MODULATING WITH ELECTRONIC CONTROL BOX mod: GAS P130/MCE LX4 EL EVO
GAS P160/MCE LX4 EL
TECHNICAL DATA GAS P130/MCE LX4 EL EVO - L.P.G. -
MODEL GAS P130/MCE LX4 EL EVO
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 258/612-1247
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 300/712-1450
Gas flow G31 (L.P.G.) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 11.6/27.6-56.2
Fuel: L.P.G. (third family)
Fuel category: I3B/P,I3+,I3P,I3B,I3R
Intermitted working operation (min. 1 stop every 24 hours) modulating
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Min. pressure gas train D2"-S L.P.G. ** [mbar] 38.9
Min. pressure gas train D2"-S MBE L.P.G. ** [mbar] --
Min. pressure gas train DN65-FS65 L.P.G. ** [mbar] 33
Min. pressure gas train DN80-FS80 L.P.G. ** [mbar] 30.2
Maximum pressure at the entry of valves (D2") [mbar] 360
Maximum pressure at the entry of valves (D2" MBE - DN65 - DN80) [mbar] 500
Nominal electric power [kW] 2.4
Fan motor [kW] 2.2
Nominal motor current absorption [A] 4.35
Nominal auxiliary absorption [A] 0.7
Power supply: 3~400V, 1/N~230V-50Hz
Electric protection degree: IP 54
NOx Class, L.P.G. (third family) 4
Noisiness *** min. - max. [dB(A)] 81-82
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law -
Control method class 3 - The measured sound pressure tolerance can be assumed to be ± 1 [dB (A)]).
GAS P130/MCE LX4 EL EVO - GAS P160/MCE LX4 EL
GAS BURNERS LOW NOX (CLASS 4) TWO STAGES PROGRESSIVE SK073074_A_en
OR MODULATING WITH ELECTRONIC CONTROL BOX mod: GAS P130/MCE LX4 EL EVO
GAS P160/MCE LX4 EL
TECHNICAL DATA GAS P160/MCE LX4 EL - NATURAL GAS -
MODEL GAS P160/MCE LX4 EL
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 206/765-1647
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 240/890-1915
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 24/89.5-192
Fuel: NATURAL GAS (second family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
Intermitted working operation (min. 1 stop every 24 hours) modulating
Environmental conditions operation / storage: -15...+40°C /…