Konten Lembar Data
GAS BURNERS TWO STAGES PROGRESSIVE OR
SK073057_B_en
MODULATING
GAS BURNERS TWO STAGES PROGRESSIVE OR MODULATING
GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
Burners for gas two stages progressive (hi-low flame) or modulating (PID fully modulating) if equipped with addition
of optional modulation kit and probe.
They are composed by: fan at high pressurisation and combustion head with adjustment at high efficiency and high
flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the
operations of setting and maintenance.
Available in the versions METHANE (natural gas) or L.P.G. (to specify at the order) on demand specific versions for
town gas, coal gas or biogas.
Gas train completely assembled and tested; complete of working valve with flow adjustment, safety valve, minimum
gas pressure switch and gas filter.
Complete of flange and gasket for installation on generator.
Available also special versions with INVERTER and ELECTRONIC BURNER CONTROL.
Fig. 1 GAS P250/MCE
Fig. 2 GAS P250/MCE
GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR
SK073057_B_en
MODULATING
TECHNICAL DATA GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
MODEL GAS P190/MCE GAS P250/MCE GAS P300/MCE
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 300/900-1900 330/1000-2500 400/1200-3000
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 349/1046-2209 384/1163-2907 465/1395-3488
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 35/105-222 39/117-292 47/140-351
Gas flow G31 (L.P.G.) min. 1°st. / min. 2°st. - max. 2°st. * [Nm³/h] 14/41-86 15/45-113 18/54-135
Fuel: NATURAL GAS (second family) - L.P.G. (third family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R) / I3B/P,I3+,I3P,I3B,I3R
Intermitted working operation (min. 1 stop every 24 hours) two stages progressive or modulating
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60 60 60
Minimum pressure gas train D2" - FS50 NATURAL GAS/L.P.G. ** [mbar] 107/43 181/94 268/120
Minimum pressure gas train DN65-FS65 NATURAL GAS/L.P.G. ** [mbar] 46/31 84/54 112/62
Minimum pressure gas train DN80-FS80 NATURAL GAS/L.P.G. ** [mbar] 30/25 56/45 72/48
Minimum pressure gas train DN100-FS100 NATURAL GAS/L.P.G. ** [mbar] 21/22 39/38 52/40
Maximum pressure at the entry of valves (Pe. max) **** [mbar] 360-500 360-500 360-500
Nominal electric power [kW] 5.8 7.8 7.8
Fan motor [kW] 5.5 7.5 7.5
Nominal motor current absorption [A] 12.3 16.3 16.3
Nominal auxiliary absorption [A] 0.6 0.6 0.6
Power supply: 3~400V,1N~230V - 50Hz
Electric protection degree: IP40 IP40 IP40
Noisiness *** min. - max. [dB(A)] 79-82 81-85 81-85
Burner weight [kg] 107 108 113
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law -
method of control Class 3 - The tollerance of the measured pressure can be taken equal to ± 1 [dB(A)]).
**** 360 mbar for "Honeywell" mod.; 500 mbar for "Dungs" and "Siemens" mod.; 200 mbar for "Krom".
OPERATING RANGE DIAGRAM GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
[mbar] 16
12
8
4
GAS P190/M GAS P250/M GAS P300/M
0
200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 [kW]
200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 [Mcal/h]
Fig. 3 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR
SK073057_B_en
MODULATING
DIMENSIONS [MM]
Fig. 4 Dimensions GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
MODEL A B C D E F G R1 R2 R3 R4 RD Gas train
weight
GAS P190/MCE - D2" FS50 360 453 974 265 145 422 363 254 509 672 504 Rp 2 21 kg
GAS P190/MCE - DN65 FS65 360 453 974 265 145 422 363 254 480 634 688 DN65 40 kg
GAS P190/MCE - DN80 FS80 360 453 974 265 145 422 363 254 480 647 708 DN80 46 kg
GAS P190/MCE - DN100 FS100 360 453 974 265 145 422 363 254 480 654 748 DN100 52 kg
GAS P250/MCE - D2" FS50 360 453 974 270 145 422 363 254 509 672 504 Rp 2 21 kg
GAS P250/MCE - DN65 FS65 360 453 974 270 145 422 363 254 480 634 688 DN65 40 kg
GAS P250/MCE - DN80 FS80 360 453 974 270 145 422 363 254 480 647 708 DN80 46 kg
GAS P250/MCE - DN100 FS100 360 453 974 270 145 422 363 254 480 654 748 DN100 52 kg
GAS P300/MCE - D2" FS50 360 453 974 300 145 422 363 254 509 672 504 Rp 2 21 kg
GAS P300/MCE - DN65 FS65 360 453 974 300 145 422 363 254 480 634 688 DN65 40 kg
GAS P300/MCE - DN80 FS80 360 453 974 300 145 422 363 254 480 647 708 DN80 46 kg
GAS P300/MCE - DN100 FS100 360 453 974 300 145 422 363 254 480 654 748 DN100 52 kg
GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR
SK073057_B_en
MODULATING
BOILER PLATE
* Suggested dimension of connection between burner
and generator.
Fig. 5 Boiler plate
MODEL L min L* L max M N min N* N max
GAS P190/MCE mm 280 280 320 M14 396 424 438
GAS P250/MCE mm 280 280 320 M14 396 424 438
GAS P300/MCE mm 310 310 320 M14 396 424 438
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TL **
GAS P190/MCE mm 495
GAS P250/MCE mm 495
GAS P300/MCE mm 460
** For different flame lengths, please contact our Technical-Sales Department.
GAS P190/MCE - GAS P250/MCE - GAS P300/MCE
GAS BURNERS TWO STAGES PROGRESSIVE OR
SK073057_B_en
MODULATING
BURNER SIGNAL DESCRIPTION
In the picture below there are indicated all the signalation present on the burner:
2
1 3
Fig. 6 Burner signal description
LEGEND
1) ON/OFF button
2) Reset from lockout button + status lamp
3) GAS valve lamp *
* In the gas train DN65-FS65, DN80-FS80 and DN100-FS100 there are 2…