Konten Lembar Data
GAS BURNERS TWO STAGES
GAS BURNERS TWO STAGES SK071011_2_B
GAS XP60/2CE EVO
Gas burners two stages with: aluminum body, fan at high pressurisation at reverse blades and combustion head with
adjustment at high efficiency and high flame stability.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the
operations of setting and maintenance.
Available in the versions METHANE (natural gas) or L.P.G. (to specify at the order) on demand specific versions for
town gas, coal gas or biogas.
Gas train completely assembled, electrically linked and tested; complete of two stages working valve with flow
adjustment, safety valve, minimum gas pressure switch and stabiliser filter of gas pressure.
Complete of flange and gasket for installation on generator.
Fig. 1 GAS XP60/2CE EVO
GAS XP60/2CE EVO
GAS BURNERS TWO STAGES SK071011_2_B
TECHNICAL DATA AND OPERATING RANGE DIAGRAM GAS XP60/2CE EVO
MODEL GAS XP60/2CE EVO
Thermalpowermin.1°st./min.2°st.-max.2°st.* [Mcal/h] 100/200-542
Thermalpowermin.1°st./min.2°st.-max.2°st.* [kW] 116/232-630
GasflowG20(NATURALGAS)min.1°st./min.2°st.-max.2°st.* [Nm³/h] 11.6/23.3-63.3
GasflowG31(L.P.G.)min.1°st./min.2°st.-max.2°st.* [Nm³/h] 4.5/9-24.5
Fuel:NATURALGAS(secondfamily)-L.P.G.(thirdfamily)
Fuelcategory: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
I3B/P,I3+,I3P,I3B,I3R
Intermittedworkingoperation(min.1stopevery24hours)twostages
Environmentalconditionsoperation/storage: -15...+40°C / -20...+70°C, umidità rel. max. 80%
Max.temperaturecombustionair [°C] 60
MinimumpressuregastrainD1"-SNATURALGAS/L.P.G.** [mbar] 115.3 / 60
MinimumpressuregastrainD1"1/4-SNATURALGAS/L.P.G.** [mbar] 54.5 / 37.4
MinimumpressuregastrainD1"1/2-SNATURALGAS/L.P.G.** [mbar] 17.7 / 21.8
Maximumpressureattheentryofvalves(Pe.max) [mbar] 360
Nominalelectricpower [W] 700
Fanmotor [W] 550
Nominalmotorcurrentabsorption [A] 1.4
Nominalauxiliaryabsorption [A] 0.5
Powersupply: 3~400V, 1N~230V - 50Hz
Electricprotectiondegree: IP 40
Noisiness***min.-max. [dB(A)] 69-72
Burnerweight**** [kg] 30.5
*Referenceconditions:Environmenttemperature20°C-Barometricpressure1013mbars-Altitude0metre(sealevel).
**Minimalfeeding-gaspressuretothegastraintogetthemaximumpoweroftheburner,consideringcounter-pressureincombustionchamberof
value0(zero).
***Measuredsonorouspressureinthelaboratorycombustion,withfunctionalburneronbetaboilerto1metreofdistance(UNIENISO3746-
ControlmethodClass3-Thetoleranceonthemeasuredsoundpressurecanbeassumedequalto±1[dB(A)]).
****Forburnerwithlongheadadd1kgtotheweight.
[mbar] 10
8
6
4
2
GAS XP60/2
0
-2
0 100 200 300 400 500 600 [kW]
Fig. 2 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the boiler.
For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance,
contact the manufacturer.
GAS XP60/2CE EVO
GAS BURNERS TWO STAGES SK071011_2_B
DIMENSIONS [MM]
A 20
A H
D
R1
G
TC-TL E
RD B C R4
R2 F
R3
Fig. 3 Dimensions GAS XP60/2CE EVO
MODEL A B C D E F G H R1 R2 R3 R4 RD TC TL
GASXP60/2CEEVO-D1"-S 200 188 276 150 99 558 416 100 193 280 338 431 Rp 1 250 335
GASXP60/2CEEVO-D1"1/4-S 200 188 276 150 99 558 416 100 193 280 338 431 Rp 1 1/4 250 335
GASXP60/2CEEVO-D1"1/2-S 200 188 276 150 99 558 416 100 193 280 346 446 Rp 1 1/2 250 335
BOILER PLATE
* Suggested dimension of connection between burner
and generator.
Fig. 4 Boiler plate
MODEL L min L* L max M N min N* N max
GASXP60/2CEEVO mm 160 160 180 M10 205 205 226
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TC TL **
GASXP60/2CEEVO mm 250 335
** For different flame lengths, please contact our Technical-Sales Department.
GAS XP60/2CE EVO
GAS BURNERS TWO STAGES SK071011_2_B
BURNER SIGNAL DESCRIPTION
In the picture below there are indicated all the signalation present on the burner:
2 1
Fig. 5 Burner signal description
LEGEND
1) ON/OFF button
2) Reset from lockout button + status lamp
The multicolor signal lamp in the lockout reset button (pos.2) is the key indicating element for visual diagnostics
and interface diagnostics.
In normal operation, the different operating states are indicated in the form of color codes; please refer to
electrical device handbook supplied with the present instructions.
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
By pressing the lockout reset button (pos.2) for more than 3 seconds, the visual diagnostics of the cause of fault
can be activated; please refer to electrical device handbook supplied with the present instructions.
For close the diagnostics mode and for switch on the burner again, it is necessary to reset the burner control.
Press the lockout reset button (pos.2) for about 1 second (<3 seconds).
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
For reset the control box press the lockout reset button (pos.2) for about 1 second (<3 seconds).
GAS XP60/2CE EVO
GAS BURNERS TWO STAGES SK071011_2_B
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Gas burners two stages.
DETAILED SPECIFICATION
Gas burner two stages composed by:
• Aluminum body;
• Fan at high pressurisationwith reverse blades;
• Combustion head with adjustment at high performance and elevated flame stability equipped with inox steel blast tube and
steel flame disc;
• Flange and insulating gasket for fixing at boiler;
• Three-phase power supply;
• Safety air pressure switch to stop the burner in lock-out in case of failed or anomalous fan operation;
• Gas train with safety valve class A, adjustment two stages valve class A;
• Optional valve proving system;
• Ionisation probe for flame detection;
• IP 40 electric protection level;
• Servomotor for air shutter and for the consent of the 2nd stage gas valve;
• Moving shutter with total closure when idle in order to reduce at the least energy losses related to boiler cooling down;
• Easy extraction of combustion head without get off the burners by bolier.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2006/42/CE - 2006/42/EG - 2006/42/EC Directive M.D.;
• GAS 2016/426/UE Regulation;
• Reference rules: EN676 (gas) – EN 746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Isomart gasket;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Noiseprotection;
• Antivibrationcouplings;
• Handlegastaps.
Theillustrationsanddatahereshownareindicative.F.B.R.BruciatoriS.r.l.reservestherighttobring,withoutanyobligationofwarning,anychangesthatwouldbeappropriatetothecontinuingdevelopmentoftheirproducts.
GAS XP60/2CE EVO