Konten Lembar Data
GAS BURNERS ONE STAGE SK_071054_E_en
GAS X0-X1-X2-X3-X4-X5CE
Gas burners one stage with: die-cast aluminum body, fan at high pressurisation, combustion head with adjustment at high efficiency
and high flame stability and protection cover with noise reduction plate.
Compact overall dimensions and disposition rationalized of the components with accessibility facilitated for the operations of
setting and maintenance.
Available in the versions METHANE (natural gas) or G.P.L. (to specify at the order) on demand specific versions for town gas, coal
gas or biogas.
Gas train completely assembled, electrically linked and tested; complete of working valve with flow adjustment, safety valve,
minimum gas pressure switch and stabiliser filter of gas pressure.
Versions F with cover of protection in steel and specific features for the application on industrial ovens and bakery ovens.
Complete of connector plug / socket 7 poles, flange and gasket for installation on generator.
Fig. 1 GAS X0CE
Fig. 2 GAS X2CE Fig. 3 GAS X3CE
Fig. 4 GAS X4CE Fig. 5 GAS X5CE
GAS X0-X1-X2-X3-X4-X5CE
GAS BURNERS ONE STAGE SK_071054_E_en
TECHNICAL DATA AND OPERATING RANGE DIAGRAM
MODEL GAS X0CE GAS X1CE GAS X2CE GAS X3CE GAS X4CE GAS X5CE
Thermal power min. - max. * [Mcal/h] 10-29.5 20-50 35-80 60-150 100-200 130-300
Thermal power min. - max. * [kW] 11.6-34.3 23.2-58.1 40.7-93 69.8-174 116-232 151-349
Gas flow G20 (NATURAL GAS) min. - max. * [Nm³/h] 1.2-3.4 2.3-5.8 4.1-9.4 7-17.5 11.7-23.4 15.2-35.1
Gas flow G31 (L.P.G.) min. - max. * [Nm³/h] 0.5-1.3 0.9-2.2 1.6-3.6 2.7-6.8 4.5-9 5.8-13.5
Fuel: NATURAL GAS (second family) - L.P.G. (third family)
Fuel category: I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R) / I3B/P,I3+,I3P,I3B,I3R
Intermitted working operation (min. 1 stop every 24 hours) one stage
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60 60 60 60 60 60
Min. pressure gas train D1/2"-S NATURAL GAS/L.P.G. ** [mbar] 7/18 14/31 - - - -
Min. pressure gas train D3/4"-S NATURAL GAS/L.P.G. ** [mbar] - - 18/24 - - -
Min. pressure gas train D1"-S NATURAL GAS/L.P.G. ** [mbar] - - - 14/31 14/21 27/33
Min. pressure gas train D1"1/4-S NATURAL GAS/L.P.G. [mbar] - - - - - 16/25
**
Max. pressure at the entry of valves (Pe. max) [mbar] 60 60 360 360 360 360
Nominal electric power [W] 80 110 130 200 226 540
Fan motor [W] 50 75 75 110 200 370
Nominal motor current absorption [A] 0.5 0.6 0.6 0.9 1.1 2.4
Power supply: 1/N~230V-50Hz
Electric protection degree: IP 40 IP 40 IP 40 IP 40 IP 40 IP 40
Noisiness *** min. - max. [dB(A)] 52-55 59-60 60-61 64-66 64-66 67-71
Burner weight **** [kg] 8 10 10 13 15 24
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 law).
**** For burners: GAS X0CE - GAS X1CE - GAS X2CE - GAS X3CE - GAS X4CE with cover in steel (F) add 3 kg to the weight.
**** For burner GAS X5CE with cover in steel (F) add 5 kg to the weight.
[mbar]
[kW]
[Mcal/h]
Fig. 6 X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN676 standards and are indicative of matching the burner to the boiler. For the correct
operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-compliance, contact the manufacturer.
GAS X0-X1-X2-X3-X4-X5CE
GAS BURNERS ONE STAGE SK_071054_E_en
DIMENSIONS [mm]
Fig. 7 Dimensions GAS X0CE - GAS X1CE - GAS X2CE - GAS X3CE - GAS X4CE
MODEL A B C D E F G H P S TC TL * R1 R2 R3 R4 RD Gas train
weight
GAS X0CE D1/2"-S 15 140 140 90 43 265 169 72 150 150 90 150 132 200 254 240 Rp 1/2 2 kg
GAS X1CE D1/2"-S 15 162 175 90 43 305 210 65 150 150 90 150 132 200 254 240 Rp 1/2 2 kg
GAS X2CE D3/4"-S 15 162 175 90 43 305 210 65 150 150 90 150 138 220 262 328 Rp 3/4 3 kg
GAS X3CE D1"-S 16 185 195 108 54 340 248 70 200 160 130 250 168 280 337 361 Rp 1 8 kg
GAS X4CE D1"-S 20 185 195 125 78 368 248 70 200 200 160 280 173 280 337 385 Rp 1 8 kg
Fig. 8 Dimensions GAS X5CE
MODEL A B C D E F G H P S TC TL * R1 R2 R3 R4 RD Gas train
weight
GAS X5CE D1"-S 18 207 213 138 98 462 310 90 200 200 250 335 160 305 362 403 Rp 1 8 kg
GAS X5CE CT-D1"-S 18 207 213 138 98 462 310 90 200 200 250 335 160 305 480 403 Rp 1 9 kg
GAS X5CE D1"1/4-S 18 207 213 138 98 462 310 90 200 200 250 335 160 305 362 450 Rp 1 1/4 8 kg
GAS X5CE CT-D1"1/4-S 18 207 213 138 98 462 310 90 200 200 250 335 160 305 480 450 Rp 1 1/4 9 kg
* For different flame lengths, please contact our Technical-Sales Department.
BOILER PLATE
** Suggested dimension of connection between burner and
generator.
Fig. 9 Boiler plate
MODEL L min L** L max M N min N** N max
GAS X0CE mm 130 150 170 M8 100 110 130
GAS X1CE mm 130 150 170 M8 100 110 130
GAS X2CE mm 130 150 170 M8 100 110 130
GAS X3CE mm 150 170 170 M8 120 130 140
GAS X4CE mm 170 205 226 M10 130 140 160
GAS X5CE mm 205 226 226 M10 150 150 180
GAS X0-X1-X2-X3-X4-X5CE
GAS BURNERS ONE STAGE SK_071054_E_en
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Gas burners on stage.
DETAILED SPECIFICATION
Gas burner one stage composed by:
• Die-cast aluminum body;
• Fan at high pressurisation;
• Combustion head with adjustment at high performance and elevated flame stability equipped with inox steel blast tube and
steel flame disc;
• Protection cover with noise reduction plate;
• Flange and insulating gasket for fixing at boiler;
• Single-phase power supply;
• Safety air pressure switch to stop the burner in case of failed or anomalous fan operation;
• Gas train with safety valve and adjustment valve;
• Ionisation probe for flame detection;
• IP 40 electric protection level.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2006/42/CE - 2006/42/EG - 2006/42/EC Directive M.D.;
• GAS 2016/426/UE Regulation;
• Reference rules: EN676 (gas) – EN 746-2 (industrial thermoprocessing equipment).
STANDARD EQUIPMENT
• Isomart gasket;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Antivibration couplings;
• Handle gas taps.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of…