We ship to Indonesia — door-to-door, customs and logistics handled by 3G Electric

Fireye Turbine Flame Sensor - Flame Sensors
FireyeFlame Sensors

Fireye Turbine Flame Sensor

Fireye 3G-OTH-02793 adalah sensor nyala api turbin yang dirancang untuk memantau nyala api pada pembangkit listrik turbin gas. Sensor ini merespons energi ultraviolet (200–400 nanometer) dan menghasilkan output…

SKU 3G-OTH-02793

Also listed as: NEDGEAC2000 · NED GEAC 2000

Brand
Fireye
Item
Turbine Flame Sensor
Category
Flame Sensors
Available to Order
Ready stock & customs handled
  • 6–10 business days door-to-door; Bea Cukai clearance typically 3–5 business days.
  • Invoicing in IDR or USD. Bank transfer and corporate PO accepted.
  • Ships to: Jakarta, Surabaya, Bandung, Medan, Batam
Trade pricing by quote — replies within 24h
Qty
WhatsApp an engineerMessage via Telegram
No account needed — your quote request goes straight to our engineers. A free account lets you track quotes and re-order faster.
Worldwide Shipping
Air & sea freight
Datasheet on Request
Technical specs
1-Day Quote
Replies within 24h

Local availability & support — Indonesia

Phone
+65 8878 8355

Technical Specifications

Fireye
Models
NED-GEAC-2000, 7FA, 9FA, 9FB, 7E, 9E, 6B, 6FA
Category
Flame Sensors
Approvals
CE, Ex, Functional Safety UL Listed SIL 3, UKCA, UL Listed

Datasheet Content

[{"filename":"CU-123-NED-GEAC-2000_Turbine_Flame_Sensor_English_2024-02-27.pdf","text":"CU-123\n February 27, 2024\n\n\n\n\n 3G-OTH-02793\n TURBINE FLAME SENSOR\n\n\n\n\nDESCRIPTION\n\nThis document describes the Fireye Turbine Flame Sensor for turbine flame monitoring applications, its installation\nand setup. The Turbine Flame Sensor responds to Ultraviolet optical energy from the flame (200-400 nanometers)\nand has a loop powered 4-20mA output representing flame brightness from a very low level. It is not sensitive to\nvisible and IR emissions from hot walls. The Fireye design basis is a total separation of the optical sensing device\nfrom the turbine without the need for expensive water or pressurized air cooling systems.\n\n\n\nAPPLICATION\n\nThe Fireye Turbine Sensor is designed to sense flame in extreme high pressure and hot environments such as those\nfound on turbine generators at power generation facilities. The sensor can be used to improve the safety, reliability\nand performance by replacing obsoleted and outdated technologies. The device has been developed and tested for\nGE Frames 6F, 7F and 9F.\n\n\nOPERATION\n\nAt the hot end is a sapphire glass window to protect the lens and fiber optic bundle from extreme pressure and\ntemperature. The fiber optic bundle transmits the UV light to the electronic assembly on the cool end, which amplifies\nthe signal and converts it to a 4-20mA output. The sensor is a loop powered 4-20mA device. The sensor monitoring\nelectronics needs to provide a voltage between 18 and 30 VDC and the sensor will vary the current between 4 and\n20mA depending upon the turbine optical signal. Nominal voltage is 24 VDC. With no optical signal from the flame\noutput will be 4mA as a minimum. Because of variation in fuel, sighting, turbine styles, etc. the output level for a\nFLAME ON is a site decision. Fireye recommends that at least 5 mA be used as a threshold level to detect FLAME\nON. The cable has multiple conductors and uses white for +24 VDC and black for the return of the 4-20mA signal.\n\n\n\n\n© Fireye 2024 1\n\f© Fireye 2024\n\fTABLE OF CONTENT\n\n\n\n\nDESCRIPTION\b���������������������������������������������������������������������������������������������������������������������������� 1\nAPPLICATION\b����������������������������������������������������������������������������������������������������������������������������� 1\nOPERATION\b�������������������������������������������������������������������������������������������������������������������������������� 1\nWARNING\b������������������������������������������������������������������������������������������������������������������������������������ 4\nDIMENSIONS\b������������������������������������������������������������������������������������������������������������������������������ 5\nSPECIFICATIONS\b����������������������������������������������������������������������������������������������������������������������� 7\nPART NUMBERS\b������������������������������������������������������������������������������������������������������������������������� 9\nPACKING\b������������������������������������������������������������������������������������������������������������������������������������� 9\nMECHANICAL INSTALLATION\b������������������������������������������������������������������������������������������������� 10\nWIRING DIAGRAM\b�������������������������������������������������������������������������������������������������������������������� 12\nOUTPUT\b������������������������������������������������������������������������������������������������������������������������������������ 13\nMAINTENANCE\b������������������������������������������������������������������������������������������������������������������������� 14\nLAST MINUTE RISK ANALYSIS (LMRA)\b���������������������������������������������������������������������������������� 15\nMAINTENANCE PROCEDURE \b������������������������������������������������������������������������������������������������ 16\nLABEL\b���������������������������������������������������������������������������������������������������������������������������������������� 18\nCERTIFICATIONS\b��������������������������������������������������������������������������������������������������������������������� 18\nNOTICE\b������������������������������������������������������������������������������������������������������������������������������������� 20\n\n\n\n\n 3\n\f WARNING\n\n\t\t\n\n\n\n !\n\t\t The equipment described in this manual is capable of causing property\n\t\t damage, severe injury, or death. It is the responsibility of the owner or operator\n\t\t to ensure that the equipment described is installed, operated and commissioned in\n\t\t compliance with the manufacturer’s instructions and all applicable codes and regulations.\n\n\n\n\nWhen this equipment is fitted to an appliance, due regard must also be given to the requirements of that\nappliance.\n\nBefore attempting to install, commission, or operate this equipment, all relevant sections of this document must\nbe read and fully understood. If in doubt about any requirements consult your supplier.\n\nInstallation, commissioning or adjustment of this product MUST be carried out by suitably trained engineers or\npersonnel qualified by training and experience.\n\nThe manufacturer of this equipment accepts no liability for any consequences resulting from inappropriate,\nnegligent or incorrect installation, commissioning or adjustment of operating parameters of the equipment.\nThere are no user serviceable parts.\n\nBefore attempting any work on this equipment or any equipment controlled by or connected to this equipment, all\nrelated electrical supplies MUST be isolated.\n\nSafety interlocks MUST NOT be removed or overridden. Any faults once detected must be corrected before the\ncontrol is operated.\nDO NOT disconnect the sensor while the circuit is energized (live), unless the area is known to be non-hazardous\nand free of explosive gases.\nThese paragraphs indicate a risk of potential serious personal injury, unless these instructions are followed\ncarefully.\n\nFailure to properly install or operate the equipment in this manual could result in significant property damage,\nsevere injury, or death. It is the responsibility of the owner or user to ensure that the equipment described is\ninstalled and operated in compliance with this manual and other system component manuals, as well with all\napplicable national and local codes.\n\nThe flame sensor seals high pressures within the turbine. The union nut must be tightened to the specified\ntorque. Insufficient torque could result in combustion gases being released into the turbine compartment.\nThe window holds pressure. The union is only for mechanical attachment.\n\nThe Turbine Sensor and its accessories are designed to operate at extreme temperatures. Do not attempt to\nwork on this device until it has reached a safe handling temperature.\n\nThe fiber optic cable cannot be bent to a radius less than 6 inches or 15 cm.\n\nDo not install a flame sensor that has a cracked window, damaged threads, or one that has been disassembled.\n\nExplosion hazard. Do not connect or disconnect when energized.\n\fDIMENSIONS\n\n\n\n 3G-OTH-02793 (GE PART #304T9240P0001): Turbine flame sensor\n Turbine flame sensor head & amp - Electronics assembly\n High pressure, high temperature window\n Stainless steel high temperature union\n UV Enhanced quartz fiber optic (fully sheathed) assembly, hot & cold end connections\n Fiber optic length: 30 feet or 9.1 meter\n\n\n\n\n 2.00″ 1.33″ 1.99″ 2.14″\n 50.8 mm 33.8 mm 50.5 mm 54.3 mm\n Ø 2.50″\n Ø 63.5 mm\n\n\n\n\n 2.91″ 30′ Ø 1.38″\n 74 mm 9140 mm Ø 34.9 mm\n\n\n ≈ 30′ 9″\n 9370 mm\n\n\n\n STAINLESS STEEL, HIGH TEMPERATURE UNION\n\n\n\n\n 3/4″ NPT\n\n\n\n\n 1.93″ Hex 1.25″\n 49.0 mm 31.7 mm\n\n HIGH PRESSURE, HIGH TEMPERATURE WINDOW\n\n 5\n\f The Cool End.... The Lens Housing....\n\n 5 PIN MALE MIL-DTL-38999\n\n LENS\n\n\n\n\n Hazardous area requirements: Det-Tronics portable turbine sensor\n The plastic “Loc Fast” retainers (supplied) must be installed UV test lamp\n over the electrical connector. Specifically designed, intrinsically safe and portable,\n battery operated source of ultraviolet radiation, emitting\n a wide band of UV radiation corresponding to the res-\n ponse of the turbine sensor.\n\n\n\n\n High temperature electrical cable & backshell with exterior\n cable braid\n\n\n\n\n© Fireye 2024\n\fSPECIFICATIONS\n\n 3G-OTH-02793\nGE PART # 304T9240P0001\nService FLAME SENSOR\nHazardous area classification Class I, Div 2 - Groups A,B,C & D, (North America). Ex II 3G Ex ec IIC T3 Gc (ATEX/IECEx)\nHousing material Stainless Steel 18-8 (304)\nMounting connection 3/4″ male NPT\nMin. operating temperature 32°F/0°C\nMin. storage temperature -40°F/-40°C\nMax. operating temperature hot end 617°F/325°C\nMax. operating temperature cool end 284°F/140°C\nHumidity 100%\nVibration Per IEC 60068-2-64, Stationary Installation, Category 3\nDetection principle Ultraviolet solid state sensor\nSensor Silicon Carbide Diode\nSensitivity 1nW/cm²@310nm\nOutput 4-20mA DC, current loop\nFlame Present Detection Time 175ms (typical < 75ms)\nFlame Failure Detection Time 175ms (typical < 75ms)\nPower supply 18-30 VDC\nReverse polarity protected YES\nElectrical connection 5-pin male MIL-DTL-38999 shell, size 15 series III hermetic, scoop proof\nSIL Rating SIL 3\nSIL Certificate EN61508\nUL Certificate UL 353, 5th Ed., Issue Date: 1994-09-23, Revision Date:…

Technical Documents

No technical documents available for this product.
Request documentation
Not sure this is the right part? Get a recommendation.

Need installation or engineering help?

Installation, commissioning, maintenance plans, system design, and bundled product + service quotes — one team handles the full scope.
Talk to an engineer

Ask a question

Fireye Products
3G Electric (S) Pte. Ltd. — Singapore

Product Description

Fireye 3G-OTH-02793 adalah sensor nyala api turbin yang dirancang untuk memantau nyala api pada pembangkit listrik turbin gas. Sensor ini merespons energi ultraviolet (200–400 nanometer) dan menghasilkan output loop-powered 4-20mA yang mewakili kecerahan nyala api. Disetujui dengan sertifikasi CE, Ex, Functional Safety UL Listed SIL 3, UKCA, dan UL Listed, sensor ini kompatibel dengan berbagai frame GE seperti 7FA, 9FA, 9FB, 7E, 9E, 6B, dan 6FA. Sebagai distributor resmi, 3G Electric menyediakan sensor turbin Fireye untuk kebutuhan peralatan pembakaran industri di Indonesia.

Supplied to Indonesia — compatible with 50 Hz installations. DHL Express delivery to Jakarta, Surabaya, Bandung, customs and duties handled door-to-door.

Frequently Asked Questions

Apa spesifikasi Fireye NED-GEAC-2000?

Fireye NED-GEAC-2000 adalah sensor nyala api turbin dengan output loop-powered 4-20mA. Sensor ini merespons sinar ultraviolet (200–400 nm) dan memerlukan tegangan suplai 18–30 VDC (nominal 24 VDC). Memiliki sertifikasi CE, Ex, Functional Safety UL Listed SIL 3, UKCA, dan UL Listed. Cocok untuk frame GE 7FA, 9FA, 9FB, 7E, 9E, 6B, dan 6FA.

Untuk apa Fireye NED-GEAC-2000 digunakan?

Sensor ini digunakan untuk memantau nyala api pada turbin gas di pembangkit listrik. Dirancang untuk lingkungan bertekanan dan bersuhu ekstrem, sensor ini menggantikan teknologi lama dengan meningkatkan keamanan dan keandalan. Output 4-20mA memungkinkan integrasi dengan sistem kontrol untuk mendeteksi status nyala api.

Bagaimana cara kerja Fireye NED-GEAC-2000?

Sensor ini menggunakan jendela safir di ujung panas untuk melindungi lensa dan bundel serat optik dari tekanan dan suhu ekstrem. Sinar UV dari nyala api ditransmisikan melalui serat optik ke rakitan elektronik di ujung dingin, yang kemudian mengubahnya menjadi sinyal 4-20mA. Kabel menggunakan putih untuk +24 VDC dan hitam untuk sinyal 4-20mA.

Di mana beli Fireye NED-GEAC-2000 di Indonesia?

Anda dapat membeli Fireye NED-GEAC-2000 melalui 3G Electric, distributor resmi yang memasok dan mengirimkan peralatan industri ke seluruh Indonesia. Kami menangani logistik dan bea cukai untuk memastikan produk sampai ke lokasi Anda. Hubungi kami untuk minta penawaran.

Apa sertifikasi yang dimiliki Fireye NED-GEAC-2000?

Fireye NED-GEAC-2000 memiliki sertifikasi CE, Ex (untuk area berbahaya), Functional Safety UL Listed SIL 3, UKCA, dan UL Listed. Sertifikasi ini memastikan sensor memenuhi standar keselamatan dan kinerja untuk aplikasi turbin gas di lingkungan industri.

Used in

Common applications for Fireye
Power-plant auxiliary boiler — M-Series II controller with UV flame scanner, programmed for gas/oil switchover and flame-presence monitoring.
Refinery process heater — MP100E programmer module managing multi-stage ignition and flame-out shutdown interlocks on high-pressure burners.
Petrochemical facility thermal oxidizer — MAUV1T UV amplifier module processing scanner signal from high-temperature burner housings with immune-response filtering.
Large-scale industrial oven (metal treating) — M-Series II with remote reset capability and dual-fuel solenoid isolation for operator safety and burner protection.
Cogeneration plant fuel-gas burner — Fireye scanner and modular controller stack integrated into BMS with remote monitoring of flame status and controller fault codes.

Fireye Products

3G Electric supplies Fireye flame sensors. We supply genuine products with in-stock availability on common SKUs, technical documentation, commissioning support, and warranty service — worldwide.

You might also need

Burners & Combustion Pumps & Compressors Spare Parts All Products

Compatible alternatives & equivalents

Cross-referenced by specification & description
NXIATS Ambient Air Temperature Sensor. The Fireye NXIATS Ambient Air Temperature Sensor is designed for reliable and accurate measurement of ambient air temperature in industrial combustion and control systems. It seamlessly integrates with the Fireye PPC6000 and NX6100 burner management systems via a Fireye-specific CANbus interface, ensuring optimal performance and data accuracy. This optional sensor enhances system functionality by providing real-time temperature monitoring, helping improve efficiency, safety, and compliance with environmental regulations
Fireye
NXIATS Ambient Air Temperature Sensor. The Fireye NXIATS Ambient Air Temperature Sensor is designed for reliable and accurate measurement of ambient air temperature in industrial combustion and control systems. It seamlessly integrates with the Fireye PPC6000 and NX6100 burner management systems via a Fireye-specific CANbus interface, ensuring optimal performance and data accuracy. This optional sensor enhances system functionality by providing real-time temperature monitoring, helping improve efficiency, safety, and compliance with environmental regulations
NX102x Gas Pressure Sensors. The NX102x Gas Pressure Sensor is an essential component for the NX6100 system, specifically designed to provide accurate and reliable gas pressure measurements in various industrial applications. Engineered for optimal performance, this sensor ensures that your gas monitoring systems operate effectively and safely
Fireye
NX102x Gas Pressure Sensors. The NX102x Gas Pressure Sensor is an essential component for the NX6100 system, specifically designed to provide accurate and reliable gas pressure measurements in various industrial applications. Engineered for optimal performance, this sensor ensures that your gas monitoring systems operate effectively and safely
Flame sensor for use in combustion safety systems. Detects flame presence in burners for boilers, furnaces, and process heaters. Replacement part for HVACR controls and thermostats
Fireye
Flame sensor for use in combustion safety systems. Detects flame presence in burners for boilers, furnaces, and process heaters. Replacement part for HVACR controls and thermostats
Flame-Monitor E120 Flame Safeguard. The Fireye® E120 Flame-Monitor™ System is specifically designed for applications requiring 220VAC power. It provides the same advanced burner management features as the E110 Flame-Monitor, with added compatibility for 220VAC power sources
Fireye
Flame-Monitor E120 Flame Safeguard. The Fireye® E120 Flame-Monitor™ System is specifically designed for applications requiring 220VAC power. It provides the same advanced burner management features as the E110 Flame-Monitor, with added compatibility for 220VAC power sources
Flame sensor for use in HVACR and burner systems. Detects flame presence and signals the control system to maintain fuel supply only when a stable flame is present, preventing unburned fuel accumulation
Fireye
Flame sensor for use in HVACR and burner systems. Detects flame presence and signals the control system to maintain fuel supply only when a stable flame is present, preventing unburned fuel accumulation
TS350 & TS752 Temperature Sensors. The BLPS, TS350 and TS752 series of pressure and temperature sensors are designed for use with the Nexus PPC4000 fuel air ratio controller and BurnerLogiX burner management system with integrated boiler control
Fireye
TS350 & TS752 Temperature Sensors. The BLPS, TS350 and TS752 series of pressure and temperature sensors are designed for use with the Nexus PPC4000 fuel air ratio controller and BurnerLogiX burner management system with integrated boiler control

More from Fireye

View all Fireye parts
69ND1 Ionization Flame Rod. The 69ND1 Flame Rod is an essential component designed for gas flame detection in high-temperature environments. Constructed from high-temperature resistant metal, this flame rod is built to perform reliably in demanding industrial applications where accurate flame detection is crucial
Fireye
69ND1 Ionization Flame Rod. The 69ND1 Flame Rod is an essential component designed for gas flame detection in high-temperature environments. Constructed from high-temperature resistant metal, this flame rod is built to perform reliably in demanding industrial applications where accurate flame detection is crucial
InTense Flame Sensor for Harsh Environments. The Fireye InTense flame sensor is designed to sense flame in extreme high pressure and hot environments such as those found on turbine generators in power generation facilities. Similar challenging environments can be found near steam boilers, waste incinerators, down-fired reformer furnaces, ground flares, rotary kiln systems, ovens and dryers in power generation facilities, oil refineries, petrochemical, ammonia plants, paper and pulp industries
Fireye
InTense Flame Sensor for Harsh Environments. The Fireye InTense flame sensor is designed to sense flame in extreme high pressure and hot environments such as those found on turbine generators in power generation facilities. Similar challenging environments can be found near steam boilers, waste incinerators, down-fired reformer furnaces, ground flares, rotary kiln systems, ovens and dryers in power generation facilities, oil refineries, petrochemical, ammonia plants, paper and pulp industries