Konten Lembar Data
HEAVY-OIL BURNERS TWO STAGES SK072029_A_en
FNDP 130/2 EVO - FNDP 160/2
Burners for heavy-oil two stages with: die-cast aluminum body, fan at high pressurisation, combustion head with
adjustment at high efficiency and high flame stability and hydraulic system of regulation combustive air on the two
stages of flame.
Disposition rationalized of the components with accessibility facilitated for operations of setting and maintenance.
Complete of flange and gasket for installation on generator, nozzles, flexible pipes, line filter electrically heated
and equipped with thermostat.
Available in versions with 2-pole or 4-pole pump motor.
Fig. FNDP 160/2
FNDP 130/2 EVO - FNDP 160/2
HEAVY-OIL BURNERS TWO STAGES SK072029_A_en
TECHNICAL DATA FNDP 130/2 EVO - FNDP 160/2
MODEL FNDP 130/2 EVO FNDP 160/2
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 34/64-137 42/80-165
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [Mcal/h] 330/621-1329 407/776-1600
Thermal power min. 1°st. / min. 2°st. - max. 2°st. * [kW] 380/730-1542 474/900-1900
Fuel: HEAVY-OIL MAX 20°E at 50°C
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 14 17
Fan motor [kW] 2.2 4
Pump motor (2-pole version) [kW] 0.55 0.55
Pump motor (4-pole version) [kW] 0.75 0.75
Nominal current absorption [A] 4.35 7.45
Nominal fan motor current absorption [A] 4.35 7.45
Nominal pump motor current absorption [A] 1.32 1.32
Nominal auxiliary absorption [A] 0.8 0.8
Resistances [kW] 11 12
Power supply: 3~400V, 1N~230V - 50Hz
Electric protection degree: IP40
Noisiness ** min-max [dBA] 82-83 84.4-85.4
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Measured sonourous pressure in the combustion lab, with funcional burner on beta boiler in a distance of 1 m (UNI EN ISO 3746).
FNDP 130/2 EVO - FNDP 160/2
HEAVY-OIL BURNERS TWO STAGES SK072029_A_en
OPERATING RANGE DIAGRAM
[mbar] 16
FNDP 130/2 EVO
14
12
10
8
6
4
2
0
200 400 600 800 1000 1200 1400 1600
[kW]
Fig. X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
[mbar] 16
FNDP 160/2
14
12
10
8
6
4
2
0
200 400 600 800 1000 1200 1400 1600 1800 2000
[kW]
Fig. X = Thermal power Y = Pression in the combustion chamber
The firing rates has been obtained based on test boilers in accordance with EN267 standards and are indicative of matching the burner to the
boiler. For the correct operation of the burner, combustion chamber dimensions must be in accordance with current regulation. In case of non-
compliance, contact the manufacturer.
FNDP 130/2 EVO - FNDP 160/2
HEAVY-OIL BURNERS TWO STAGES SK072029_A_en
DIMENSIONS [MM]
40 183
F
320 D
320 N E
A B TC - TL C1 - C2 *
Fig. Dimensions
MODEL A B C1 C2 * D E F N
FNDP 130/2 EVO 460 407 960 1545 209 510 211 20
FNDP 160/2 460 407 960 1545 209 510 211 20
* Overall dimension with the burner out in position of maintenance.
BOILER PLATE
** Suggested dimension of connection between burner
and generator.
Fig. Boiler plate
MODEL L min L max M N min N** N max
FNDP 130/2 EVO mm 340 368 M14 220 220 250
FNDP 160/2 mm 340 368 M14 220 220 250
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case,
it must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area
between the flame tube and front door with refractory material. This protection material must not impede flame
tube extraction.
MODEL TC TL ***
FNDP 130/2 EVO mm 210 400
FNDP 160/2 mm 210 400
*** For different flame lengths, please contact our Technical-Sales Department.
FNDP 130/2 EVO - FNDP 160/2
HEAVY-OIL BURNERS TWO STAGES SK072029_A_en
PRODUCT SPECIFICATION
PRODUCT SPECIFICATION
Heavy-oil burners two stages.
DETAILED SPECIFICATION
Heavy-oil burners two stages,composed by:
• Die-cast aluminum body;
• Fan at high pressurisation, at reverse blades for FNDP 130/2 EVO;
• Combustion head with adjustment at high performance and elevated flame stability;
• Flange and insulating gasket for fixing at boiler;
• Three-phase power supply;
• Photodiode for flame detection;
• IP 40 electric protection level;
• Supports and tierods for burner extraction;
• Easy extraction of combustion head without get off the burners by bolier;
• Pump controlled by dedicated electric motor; available in 2-pole or 4-pole version;
• Safety air pressure switch to stop the burner in lock-out (by stopping the pump motor) in case of failed or anomalous fan
operation;
• Thermostats for regulating: temperature of 1st resistance group, temperature of 2nd resistance group, minimum temperature.
CONFORMING TO:
• CE rules;
• 2014/30/UE Directive E.M.C.;
• 2014/35/UE Directive L.V.;
• 2006/42/CE - 2006/42/EG - 2006/42/EC Directive MAC;
• 2014/68/EU (art.4, par.3) Directive P.E.D.;
• Reference rules: EN267 (liquid fuel) - EN746-2 (industrial thermoprocessing equipment)
STANDARD EQUIPMENT
• Flexible hoses for connection;
• Line filter electrically heated and equipped with a thermostat;
• Isomart gasket;
• Nozzles;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Noise protection.
The illustrations and data here shown are indicative. F.B.R. Bruciatori S.r.l. reserves the right to bring, without any obligation of warning, any changes that would be appropriate to the continuing development of their products
FNDP 130/2 EVO - FNDP 160/2