Konten Lembar Data
COMPACT PRESSURE SWITCH
3G-CBM-01177-10
CONTENT
APPLICATION / FEATURES CHARACTERISTICS
DIMENSIONS
APPLICATION / FEATURES
The COMBUPx compact pressure switch is specially designed for monitoring air or gas pressure in gas-fired
equipment and systems, such as burners.
• It allows for effective monitoring of pressure in gas pipelines. • Its compact size makes it very easy
to install, even in confined spaces. • Thanks to its ergonomic structure, the user can adjust the operating
parameters himself. • It is available in several versions, offering different pressure settings to suit
various installation needs.
• COMBUPx can be configured as minimum or maximum pressure switches,
depending on system requirements.
• The set point is adjustable up to 500 mbar, independent of the range
effective.
• It can operate under a continuous working pressure of up to 600 mbar. • It is
compatible with gases of families 1, 2 and 3, as well as with other neutral gases
non-corrosive.
• Fully compatible with other similar products, it integrates easily into existing systems.
FEATURES
Kind Adjustable
Body Cast aluminum
Materials
Diaphragm HNBR
Switching contact Ag-SnO2
Setpoint adjustment Rotary graduated knob
Working temperature: -15 ~ +60 ÿ,
Temperature
Storage temperature: -20~+80 ÿ
Min. AC efficiency 24 V max. 250 V
Switching voltage
DC min. 24 V max. 48 V
Cutting power 6A AC max
Electrical power
AC eff max. 6 A for cos 1 AC eff
max. 2 A for cos 0.6 AC eff min. 20 mA
Switching current DC max. 1 A DC min.
20 mA
Kind Gases family 1, 2 and 3 according to EN 437+A1:2009; Air
02
FEATURES
Model COMBUP3 COMBUP10 COMBUP50 COMBUP150 COMBUP500
1.0 ~ 3.0 2.0 ~ 10.0 5.0 ~ 50.0 5.0 ~ 150.0 100 ~ 500
Pressure range (mbar) The COMBUP150 may deviate slightly from the setting tolerance in the range of 5.0 to 30 mbar
Factory setting (mbar) 1.0 2.0 5.0 5.0 100
ÿ1.0 mbar ÿ1.5 mbar ÿ 3.0 mbar ÿ 6 mbar ÿ 20 mbar
Differential pressure (ÿP)max
Allowable pressure (mbar) 500 (50 kPa) 600 (60 kPa)
Terminal -
800 VAC/1 min
Rigidity Terminal
dielectric Terminal -
1500 VAC/1 min
Earth
Insulation resistance 100ÿ , Min. DC500V Megger
Adjusting the tolerance to ± 15% deviation between the switching point and the setpoint, which adjusts the pressure point in
room temperature the event of a pressure drop when the membrane is in the vertical position.
Allowable deviation Permissible deviation from the set value ÿ ± 15% during the service life test according to EN 1854
Electrical connection 3-pin connector according to DIN - EN 175 301 - 803 (without earth connection).
Pressure measurement ø 9, length 10 mm, with threaded cap (test tip integrated in a ø9 metal housing)
Process connection Standard: Centered on the bottom of the case, 1/4'' Female thread
Degree of protection IP 54 according to IEC 529 (EN60529)
Leak ÿ Sealing Pmax X1.5 for 1 minute or Standard (EN1854 (7.2.2)
The operating pressure drift must be within ± 15% before and after the endurance test.
Drift
Guarantee 1 year
Noticed
In the following cases, we recommend that you contact us before use.
1. Use only sufficiently cured silicone tubes.
2. Vapors containing silicone may impair the operation of electrical contacts. In case of low switching capacities, e.g. 24 V, less than 20 mA, we recommend using an RC module or an electronic switch
(non-contact switch) in air containing silicone or oil.
3. A fall or impact may compromise the safety functions. These products must not be put into service, even if they show no damage.
4. In case of high humidity or aggressive gaseous components (H2S), we recommend using a pressure switch with gold contact.
5. Closed-circuit current monitoring is recommended under severe operating conditions.
6. Do not operate at a pressure lower than the minimum set pressure.
03
Connection diagram
Minimum pressure switch When the pressure falls Maximum pressure switch When the
Function below the set value, NO opens and NC closes pressure exceeds the set value,
NC opens and NO closes
when used as...
Connection by connector according to
DIN 43650
Installation position
Standard installation position
If a different installation position is used, be careful
at modified operating points
When installed horizontally, the pressure switch switches to the
highest pressure.
When installed horizontally above the head, the
pressure switch switches to the lowest pressure.
When installed in an installation position
intermediate, the pressure switch switches to the highest pressure
high.
04
DIMENSIONS
Fig 1. Gas pressure switch (V)
05
PRESSOSTAT COMPACT
3G-CBM-01177-10
CONTENU
APPLICATION / FONCTIONNALITÉS
CARACTÉRISTIQUES
DIMENSIONS
APPLICATION / FONCTIONNALITÉS
Le pressostat compact COMBUPx est spécialement conçu pour la surveillance de la
pression de l’air ou des gaz dans les panoplies et les équipements à gaz, tels que les
brûleurs.
• Il permet de surveiller efficacement la pression dans les canalisations de gaz.
• De taille compacte, il est très facile à installer, même dans des espaces restreints.
• Grâce à sa structure ergonomique, l’utilisateur peut ajuster lui-même les paramètres
de fonctionnement.
• Il existe en plusieurs versions, offrant différents réglages de pression pour répondre à
divers besoins d’installation.
• Les COMBUPx peuvent être configurés comme pressostats de minimum ou de
maximum, en fonction des exigences du système.
• Le point de consigne est ajustable jusqu’à 500 mbar, indépendamment de la plage
effective.
• Il peut fonctionner sous une pression de service continue allant jusqu’à 600 mbar.
• Il est compatible avec les gaz des familles 1, 2 et 3, ainsi qu’avec d'autres gaz neutres
non corrosifs.
• Entièrement compatible avec d'autres produits similaires, il s'intègre facilement dans
des systèmes existants.
CARACTÉRISTIQUES
Type Réglable
Corps Fonte d'aluminium
Matériels
Diaphragme HNBR
Contact de commutation Ag-SnO2
Réglage consigne Bouton gradué rotatif
Température Température de service : -15 ~ +60 ℃,
Température de stockage : - 20 ~ +80 ℃
Efficacité CA min. 24 V max. 250 V
Tension de commutation
CC min. 24 V max. 48 V
Pouvoir de coupure 6A AC max
Puissance électrique
AC eff max. 6 A pour cos 1
AC eff. max. 2 A pour cos 0,6
Courant de commutation AC eff. min. 20 mA
DC max. 1 A
DC min. 20 mA
Type Gaz famille 1, 2 et 3 selon EN 437+A1:2009 ; Air
02
CARACTÉRISTIQUES
Modèle COMBUP3 COMBUP10 COMBUP50 COMBUP150 COMBUP500
1,0 ~ 3,0 2,0 ~ 10,0 5,0 ~ 50,0 5,0 ~ 150,0 100 ~ 500
Plage de pression (mbar) Le COMBUP150 peut s'écarter légèrement de la tolérance de réglage dans la plage de 5,0 à 30
mbar
Réglage d'usine (mbar) 1,0 2,0 5,0 5,0 100
Pression différentielle (△P)max ≤1,0 mbar ≤1,5 mbar ≤ 3,0 mbar ≤ 6 mbar ≤ 20 mbar
Pression admissible (mbar) 500 (50 kPa) 600 (60 kPa)
Terminal -
Rigidité 800 VCA/1 min
Terminal
diélectrique Terminal -…