Konten Lembar Data
LIGHT-OIL BURNERS TWO STAGES SK070002_E_en
STAGES TWO BURNERS
LIGHT-OIL
FGP 50/2 EVO-3
Burners for light-oil two stages.
They are composed by:fanathighpressurisationandreverseblades,combustion headwithadjustmentathigh
efficiencyand highflamestabilityandhydraulicsystemofregulationcombustiveaironthetwostagesofflame.
Compact overalldimensionsanddispositionrationalizedofthecomponentswithaccessibilityfacilitatedforthe
operationsofsettingandmaintenance.
Completeofnozzles,flexible hoses andlinefilter.
Complete offlangeandgasketforinstallationongenerator.
Fig. 1 FGP 50/2 EVO-3
FGP 50/2 EVO-3
LIGHT-OIL BURNERS TWO STAGES SK070002_E_en
TECHNICALDATA FGP 50/2 EVO-3
MODEL FGP 50/2 EVO-3
Flow min. 1°st. / min. 2°st. - max. 2°st. * [kg/h] 9.9/20-53.1
Thermal power min. 1°st. / min. 2°st. - [Mcal/h] 100.1/204-541.8
max. 2°st. *
Thermal power min. 1°st. / min. 2°st. - [kW] 117.4/237-630
max. 2°st. *
Fuel: LIGHT-OIL 1.5°E at 20°C = 6.2 cSt = 35 sec Redwood N°1
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage: -15...+40°C / -20...+70°C, rel. humidity max. 80%
Max. temperature combustion air [°C] 60
Nominal electric power [kW] 1.1
Fan motor [kW] 0.74
Nominal motor current absorption [A] 1.8
Nominal auxiliary absorption [A] 0.3
Power supply: 3~400V, 1N~230V - 50Hz
Electric protection degree: IP 40
Noisiness**min-max [dBA] 71-73
Burnerweight*** [kg] 31
*Referenceconditions:Environmenttemperature 20°C-Barometricpressure1013mbars-0 (zero) Height meters above mean sea level.
**Sound power level detected at a distance of 1 meter in the combustion lab with burner working on boiler (UNI EN ISO 3746).
***ForburnerFGP 50/2 EVO-3 longheadadd1kgtotheweight.
OPERATING RANGE DIAGRAM FGP 50/2 EVO-3
[mbar] 12
10
8
6
4
2
0
0 100 200 300 400 500 600 700 [kW]
Fig. 2 X=ThermalpowerY=Pressioninthecombustionchamber
ThefiringrateshasbeenobtainedbasedontestboilersinaccordancewithEN267standardsandareindicativeofmatchingtheburnertotheboiler.
Forthecorrectoperationoftheburner,combustionchamberdimensionsmustbeinaccordancewithcurrentregulation.Incaseofnon-compliance,
contactthemanufacturer.
FGP 50/2 EVO-3
LIGHT-OIL BURNERS TWO STAGES SK070002_E_en
DIMENSIONS [MM]
O
F
P C
20
E
TC - TL
A B D
Fig. 3 DimensionsFGP 50/2 EVO-3
MODEL A B C D E F O P
FGP 50/2 EVO-3 187 314 150 558 417 100 207 200
* see "flame tube length"
FGP 50/2 EVO-3
LIGHT-OIL BURNERS TWO STAGES SK070002_E_en
BOILER PLATE
* Suggested dimension of connection between burner
and generator.
Fig. 4 Boilerplate
MODEL L min L max M N min N* N max
FGP 50/2 EVO-3 mm 205 226 M10 160 160 180
FLAME TUBE LENGTH
Flame tube length must be selected based on the specifications supplied by boiler manufacturer and, in any case, it
must be greater than the thickness of the boiler door included its insulation.
In case of boilers with flame inversion or front flue combustion chambers, it is necessary to insulate the area between
the flame tube and front door with refractory material. This protection material must not impede flame tube extraction.
MODEL TC TL **
FGP 50/2 EVO-3 mm 250 335
** For different flame lengths, please contact our Technical-Sales Department.
FGP 50/2 EVO-3
LIGHT-OIL BURNERS TWO STAGES SK070002_E_en
BURNER SIGNAL DESCRIPTION
In the picture below there are indicated all the signalation present on the burner:
2 1
Fig. 5 Burnersignaldescription
LEGEND
1) ON/OFFbutton
2) Resetfromlockoutbutton+statuslamp
The multicolor signal lamp in the lockout reset button (pos.2) is the key indicating element for visual diagnostics
and interface diagnostics.
In normal operation, the different operating states are indicated in the form of color codes; please refer to
electrical device handbook supplied with the present instructions.
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
By pressing the lockout reset button (pos.2) for more than 3 seconds, the visual diagnostics of the cause of fault
can be activated; please refer to electrical device handbook supplied with the present instructions.
For close the diagnostics mode and for switch on the burner again, it is necessary to reset the burner control.
Press the lockout reset button (pos.2) for about 1 second (<3 seconds).
After a non-alterable lockout, the red signal lamp in the lockout reset button (pos.2) lights up.
For reset the control box press the lockout reset button (pos.2) for about 1 second (<3 seconds).
FGP 50/2 EVO-3
LIGHT-OIL BURNERS TWO STAGES SK070002_E_en
PRODUCT SPECIFICATION
SHORT DESCRIPTION
Light-oil burners two stages.
DETAILED SPECIFICATION
Light-oil burner two stages composed by:
• Fanathighpressurisationandreverseblades;
• Combustionheadwithadjustmentathighperformanceandelevatedflamestability;
• Flangeandinsulatinggasketforfixingatboiler;
• Three-phasepowersupply;
• Photoresistanceforflamedetection;
• IP40electricprotectionlevel;
• Easyextractionofcombustionheadwithoutgetofftheburnersbybolier.
CONFORMING TO:
• CErules;
• 2014/30/UEDirectiveE.M.C.;
• 2014/35/UEDirectiveL.V.;
• 2006/42/CEDirectiveM.D.;
• 2014/68/UE(ART.4,PAR.3)DirectiveP.E.D.;
• Referencerules:EN267(liquidfuel)-EN746-2(industrialthermoprocessingequipment).
STANDARD EQUIPMENT
• Flexible hoses for connection;
• Line filter;
• Isomart gasket;
• Nozzles;
• Flange with insulating gasket;
• Burner nameplate;
• Warranty;
• Instruction handbook for installation, use and maintenance.
OPTIONAL
• Noiseprotection.
Theillustrationsanddatahereshownareindicative.F.B.R.BruciatoriS.r.l.reservestherighttobring,withoutanyobligationofwarning,anychangesthatwouldbeappropriatetothecontinuingdevelopmentoftheirproducts.